Marca: Honeywell

SKU: R7140G2008/U

Product Specifications

ApplicationUpgrade Replacement Programming Control for R4140 or BC7000Dimensions (in.)7 in. wide x 6 5/32 high x 5 3/4 in. deepDimensions (mm)177 mm wide x 156 mm high x 146 mm deepWeight (lb)3 lb 1 ozWeight (kg)1.4 kgCommentsLHL-LF ProvenFrequency50 Hz; 60 Hz (±10%)Approvals, Underwriters Laboratories Inc.Component Recognized, File No. MP268; Guide No. MCCZ.Voltage120 Vac (+10, -15%)Shipping and Storage Temperature Range (F)-40 F to +140 FShipping and Storage Temperature Range (C)-40 C to +60 CApprovals, Federal Communications CommissionFCC Part 15, Class B, Emissions.Flame Establishing Period – Pilot4 sec or 10 secFlame Establishing Period – Main10 sec, or 15 sec, or 30 sec, or IntermittentInterlocksRunningPreignitionYesPrePurgeDetermined by ST7800A Purge Timer CardPostPurge15 secEarly Spark TerminationYes, 5 secRequired ComponentsR7847, R7848, R7849, R7851, R7852, R7861, or R7886 Flame Signal Amplifier. ST7800 Plug-in Purge Timer Card.AirFlow CheckUser selectablePilot TypeInterrupted or IntermittentVibration0.5 G environment

Solicite su cotización o para mayor información de los productos, contáctenos: